MI 3105 EurotestXA

MI 3105 EurotestXA represents a professional industrial multifunction electrical installation safety tester that performs a complete set of installation safety tests according to IEC/EN 61557. It supports Programmable AUTOSEQUENCE ® testing of the TN, TT and IT earthing systems. On-line voltage monitoring, phase sequence testing, earth resistance and lightning protection testing with two clamps, continuity, insulation, ISFL and the IMD tests, TRMS current, illuminance and more. Instrument is equipped with integrated characteristics of Fuses and RCDs for PASS / FAIL evaluation of test results. EuroLink PRO and Eurolink Android softwares enabling generation of professional test reports.


AUTOSEQUENCE(R) predefined tests:

  • AUTOSEQUENCE Programmable;
  • Auto TT (U, Zln, Zs, Uc);
  • Auto TN/RCD (U, Zln, Zs, Rpe);
  • Auto TN (U, Zln, Zlpe, Rpe);
  • Auto IT (U, Zln, Isc, Isfl, IMD).

Measuring Functions:

  • Insulation resistance with DC voltage from 50 V to 1000 V;
  • Insulation resistance Automatic L-N, L-PE, N-PE;
  • Continuity of PE with 200 mA DC test current with polarity change;
  • Continuity of PE with 7 mA test current without RCD tripping;
  • Line/Loop impedance;
  • Loop impedance with Trip Lock RCD function;
  • TRMS voltage and frequency;
  • Phase sequence;
  • RCD testing (general and selective, type AC, A, F, B, B+);
  • Automated RCD testing procedure.
  • Earth resistance (3-wire and 2-clamps method);
  • Specific earth resistance with Ro-adapter (option);
  • TRMS leakage and load currents (option);
  • First fault leakage current (ISFL);
  • Testing of Insulation Monitoring Devices (IMDs);
  • Varistor test;
  • Illumination (option).

Other features:

  • Z 290 A Industrial Hi resolution Impedance Adapter support.
  • Built-in help screens for referencing on site.
  • Built-in fuse tables for automatic evaluation of the line / loop impedance result.
  • Monitoring of all 3 voltages in real-time.
  • Automatic polarity reversal on continuity test.
  • Loop impedance test without tripping the RCD.
  • Built-in charger and rechargeable batteries as standard accessory.
  • BlueTooth dongle support for communication with PC,  Android tablets and Smart Phones.

 

Powerful PC SW EuroLink PRO included in standard delivery, enables uploading of structure of installation and downloading of results and parameters with PASS / FAIL evaluation status.

PC SW EuroLink PRO is a strong creating tool of professional Visual Inspection Report and Testing Result Report.

Standards Applied

Functionality

  • EN 61557
  • DIN 5032

Other reference standards

  • IEC/EN 60364-4-41;
  • EN 61008;
  • EN 61009;
  • BS 7671;
  • AS/NZ 3017;
  • CEI 64.8;
  • HD 384;
  • VDE 413

Electromagnetic compatibility

  • EN 61326

Safety (LVD)

  • EN 61010-1;
  • EN 61010-031
  • EN 31010-2-030
  • EN 31010-2-032

Android APP

From Scan to Test in Seconds

Learn more...

You Tube

METREL - AUTOSEQUENCE Video presentation.

Learn more...

MI 3105 EurotestXA

Go to official Metrel site of product EurotestXA MI 3105

Learn more...

Applications

The request and the decision to purchase the appropriate measuring equipment is produced on needs for determining the parameters and measurable quantities. The introduction of new technologies, in providing adequate safety in various areas, and providing quality services.


Scope of Application

  • Low Voltage Electrical Installation Safety.
  • Low Voltage Electrical Installation Designers needs.
  • Facility Management, maintenance and care of commercial or institutional buildings, such as hospitals.
  • Hotels, office complexes, arenas, schools or convention centres.
  • Low voltage installations maintenance, Preventive and Predictive maintenance, Corrective maintenance / Reactive repairs.
  • Periodic Statutory Testing and Inspections.
  • Fire Safety and Hazards, Troubleshooting of Overloaded electrical systems, hot wiring or connections, failed components.
  • Electrical Safety in Working places.
  • Electrical Safety in Public Areas.

AUTOSEQUENCE testing

Metrel's unique AUTOSEQUENCE®  testing makes evaluation and certification of safety, operational quality and fire protection of electrical installations much easier. EurotestXA with programmed AUTOSEQUENCE will execute all requested tests while taking care of irregular installation conditions, and display tests results accompanied with PASS/FAIL decision.

The main benefits of the AUTOSEQUENCE testing are:

  • Save time and speed-up operator's work: up to 5 times faster testing than with manual procedures.
  • Make test operation simple and comprehensible: one single press of the TEST button for all the necessary operations. EurotestXA guide the operator through whole procedure.
  • Increase reliabillity: up to 50 acquired test results with corresponding parameters are saved at once. Programmed test sequences guarantee that none of necessary tests will be forgotten ever.
  • Immediate certification: delivering automatic evaluation of safety with pass/fail indication for each performed test and overall test results simultaneously.
  • Take the troubles out of report creation: EurotestXA PC software gives you all the necessary tools to generate standardized test report in less than a minute.
  • Safe usage: automatically detects possible safety hazards for the operator, by means of continous monitoring of terminal voltages and by PE touch electrode TEST key, which are active in all test functions. 

PC Software EuroLink PRO and EuroLink PRO Plus

The EuroLink PRO / PRO Plus software works in conjunction with Metrel’s downloadable installation testers. The software automatically finds the instrument and allows the test engineer to download test results saved on the instrument, review the results, relocate test results (if required), print test reports and print installation structures for storing in the distribution board. With the more advanced Metrel installation testers, structures can be built with the software and uploaded to the instrument for easy installation navigation while performing on-site testing. Additionally the EuroLink PRO Plus software offers the ability to automatically generate professional PRO Plus Reports.

The main benefits of the EuroLink PRO/PRO Plus software are:

  • Automatic recognition of the instrument: when connecting your instrument to the PC it is automatically recognized by the software.
  • Simple graphical visualisation of the installation structure: enables graphical representation of the tested installation which makes it easy to navigate in the installation.
  • 10-level structures: in conjunction with MI 3105 and MI 3101 PC software enables creating the electrical installation structures with up to 10 levels and 4 levels for other models.
  • Rearranging of structures: the elements of the structure can be relocated and renamed.
  • Installation structures printing: structures can be printed and stored in the distribution board for easier later identification of the installation elements.
  • Structures upload: the installation structure can be created in advance on the PC and then simply uploaded to your tester MI 3108, MI 3109, MI 3105, MI 3101, MI 3102H CL, MI 3102H BT, MI 3102 BT, MI 3100 SE, MI 3125 BT, MI 3125B.
  • Export of test results: test results in text format can be exported to other programs (MS Excel, MS Word).
  • Automatic PRO Test Report generation: enables automatic generation of PRO Test Report (low, medium and high detailed).
  • Automatic PRO Plus Test Report generation (PRO Plus version only): enables automatic generation of PRO Plus Test Report which include visual inspection of tested object and test results in tabular form.
  • Suport of EuroLink Android: suports extended file format from EuroLink Android App.

Key features of PRO Plus Test Reports:

  • Downloaded test results are automatically inserted onto PRO Plus forms.
  • Allows to fill out visual inspection form for tested fuse cabinet or earthing system.
  • Automatically selects worst case test results for form completion.
  • Easy test report generation and reviewing facilities.
  • PC SW EuroLink PRO is password protected for the following Metrel instruments: MI 3121, MI 3121H, MI 3122 and MI 3123.
  • PC SW EuroLink PRO Plus is password protected for all Metrel installation testers.

Communication Tool EuroLink Android connecting Metrel Eurotest Instruments and EuroLink PCSW.

  • Create Structure of Electrical Installation at the site.
  • Upload Structure of Electrical Installation to your instrument and download data to EuroLink Android A 1431.
  • Add Video or Audio Files, Pictures or Edit Comments to Installation Structure at the site.
  • Transfer Data, Share files or Send them through your Tablet or Smart Phone Tools to your Office for further manipulation.

Features

  • Supported are Metrel instruments with built-in Bluetooth
    - EurotestXE MI 3102H BT,
    - EurotestXE MI 3102 BT,
    - EurotestCOMBO MI 3125BT

  • or with external Bluetooth dongle:
    - EurotestXA MI 3105,
    - EurotestAT MI 3101,
    - EurotestCOMBO MI 3125B,
    - EurotestEASI MI 3100 SE,
    - EurotestPV MI 3108.

  • Compatible with EuroLink PRO and EuroLinkPRO Plus PC software.




EuroLink Android A 1431

  • Create Reports already at the site of testing!
  • Add Pictures, Audio, or Video Files and Comments!
  • Share or Send!

 

 

Technical specification

Function

Measuring range

Resolution

Accuracy

Insulation resistance (EN 61557-2)

U= 50, 100, 250 VDC:

R: 0.00 M … 19.99 M

20.0 M … 99.9 M

100.0 M … 199.9 M

U= 500 VDC, 1 kVDC:

R: 0.00 M … 19.99 M

20.0 M … 199.9 M

200 M … 299 M

300 M … 1000 M

 

0.01 M

0.1 M

0.1 M

 

0.01 M

0.1 M

1 M

1 M

 

±(5 % of reading + 5 digits)

±10 % of reading

±20 % of reading

 

±(5 % of reading + 3 digits)

±10 % of reading

±10 % of reading

±20 % of reading

Continuity 200 mA of PE conductor

with polarity change (EN 61557-4)

0.00 … 19.99

20.0 … 199.9

200 … 1999

2000 … 9999

0.01

0.1

1

1

±(3 % of reading + 3 digits)

±5 % of reading

±5 % of reading

Indicator only

Low resistance continuity measurement, test current 7 mA (Continuous measurement)

0.0 … 19.9

20 … 1999

2000 … 9999

0.1

1

1

±(5 % of reading + 3 digits)

±(5 % of reading + 3 digits)

Indicator only

Line impedance (EN 61557-3)

0.00 … 9.99

10.0 … 99.9

100 … 999

1.00 k … 9.99 k

10.0 k … 19.9 k

0.01

0.1

1

10

100

±(5 % of reading + 5 digits)

Voltage drop

0.0 % … 99.9 %

0.1 %

Consider accuracy of line impedance

Loop impedance (EN 61557-3)

0.00 … 9.99

10.0 … 99.9

100 … 19999

0.01

0.1

1

±(5 % of reading + 5 digits)

Voltage

0 V … 550 V

1 V

±(2 % of reading + 2 digits)

Frequency

0.00 Hz … 999.99 Hz

0.01 Hz

±(0.2 % of reading + 1 digit)

Phase sequence (EN 61557-7)

1.2.3 or 3.2.1

 

 

RCD testing (EN 61557-6)

IN: 10 mA, 30 mA, 100 mA,
300 mA,
500 mA, 1 A

 

 

- Contact voltage UC

0.0 V … 19.9 V

20.0 V … 99.9 V

0.1 V

0.1 V

(-0 % / +15 %) of reading ± 10 digits

(-0 % / +15 %) of reading

- Trip-out time

0.0 ms … 40.0 ms

0.0 ms … max. time

0.1 ms

0.1 ms

±1 ms

±3 ms

- Trip-out current

0.2 x IN … 1.1 x IN (AC type)

0.2 x IN … 1.5 x IN (A type, IN 30 mA)

0.2 x IN … 2.2 x IN (A type, IN < 30 mA)

0.2 x IN … 2.2 x IN (B type)

0.05 x IN

0.05 x IN

0.05 x IN

0.05 x IN

±0.1 x IN

±0.1 x IN

±0.1 x IN

±0.1 x IN

Earth resistance (EN 61557-5) (three-wire method; one clamp method)

0.00 … 19.99

20.0 … 199.9

200 … 1999

2000 … 9999

0.01

0.1

1

1

±(3 % of reading + 3 digits)

±(3 % of reading + 3 digits)

±5 % of reading

±10 % of reading

Earth resistance (two clamps method)

0.00 … 19.99

20.0 … 30.0

30.1 … 39.9

0.01

0.1

0.1

±(10 % of reading + 10 digits)

±20 % of reading

±30 % of reading

Specific earth resistance

0.0 m … 99.9 m

100 m … 999 m

1.00 km … 9.99 km

10.0 km … 99.9 km

> 100 km

0.1 m

1 m

0.01 km

0.1 km

1 km

±5 % of reading

±5 % of reading

±5 % of reading; ±10 % of reading

±10 % of reading; ±20 % of reading

±20 % of reading

TRMS Current

0.0 mA … 99.9 mA

100 mA … 999 mA

1.00 A … 19.99 A

0.1 mA

1 mA

0.01 A

±(3 % of reading + 3 digits)

Illuminance (Type B)

0.00 lux … 19.99 lux

20.0 lux … 199.9 lux

200 lux … 1999 lux

2.00 klux … 19.99 klux

0.01 lux

0.1 lux

1 lux

10 lux

±(5 % of reading + 2 digits)

Varistor Test

0 … 625 VAC; 0 … 1000 VDC

1 V

±(3 % of reading + 3 digits)

Power supply

6 x 1.2 V rechargeable batteries, type AA

Overvoltage category

CAT III / 600 V; CAT IV / 300 V

Protection class

Double insulation

COM port

RS232 and USB

Dimensions

230 x 103 x 115 mm

Weight

1.3 kg

MI 3105 Standard set

  • Instrument EurotestXA
  • PC Software EuroLink PRO 
  • Plug commander, 1.5 m
  • Test lead, 3 x 1.5 m
  • Power supply adapter + 6 NiMH rechargeable batteries, type AA
  • Test probe, 3 pcs (blue, black, green)
  • Crocodile clip, 3 pcs (blue, black, green)
  • RS232 - PS/2 cable
  • USB cable
  • Soft carrying bag
  • Soft carrying neck belt
  • Short instruction manual
  • Instruction manual on CD
  • Handbook on CD
  • Calibration certificate

MI 3105 Euro set

  • Instrument EurotestXA
  • Current clamp A 1018 (low range, leakage)
  • PC Software EuroLink PRO Plus
  • Plug commander, 1.5 m
  • Test lead, 3 x 1.5 m
  • Power supply adapter + 6 NiMH rechargeable batteries, type AA
  • Test probe, 3 pcs (blue, black, green)
  • Crocodile clip, 3 pcs (blue, black, green)
  • RS232 - PS/2 cable
  • USB cable
  • Soft carrying bag
  • Soft carrying neck belt
  • Short instruction manual
  • Instruction manual on CD
  • Handbook on CD
  • Calibration certificate

Download files

File type Title Language Version Release date Notes File type Size File
Manual MI 3105 EurotestXA   5.4, HW 5 16.10.2013

20 751 833

pdf 2.02 MB Download
Datasheet MI 3105 EurotestXA   1.0 28.12.2010   pdf 2.48 MB Download
Datasheet PC SW EuroLink PRO   1.0 13.3.2014   pdf 915.07 KB Download
PC software EuroLink PRO EU   4.35 7.3.2018

Readme

zip 60.05 MB Download
USB driver USB driver   2.06.00 28.12.2010

Readme

zip 2.99 MB Download
Note! Subject to technical change without notice.

Optional accessories:

  • A 1292
    A 1292 Upgrade code Eurolink PRO to EuroLink PRO Plus
  • A 1012
    A 1012 Test lead, green, 4 m
  • A 1018
    A 1018 Current clamp (low range leakage)
  • A 1019
    A 1019 Current clamp
  • A 1074
    A 1074 Mini current clamp 200 A - 0.2 A
  • A 1110
    A 1110 Three phase adapter
  • A 1111
    A 1111 Three phase adapter with switch
  • A 1143
    A 1143 Euro Z 290 A
  • A 1160
    A 1160 Fast charger for 6 AA batteries with a set of 6 NiMH bateries, type AA
  • A 1169
    A 1169 Fast charger for AA, C, D and 9 V block bateries
  • A 1172
    A 1172 Luxmeter sensor type B (PS/2)
  • A 1173
    A 1173 Luxmeter sensor Type C (PS/2)
  • A 1191
    A 1191 Receiver R10K
  • A 1192
    A 1192 Selective probe for R10K
  • A 1197
    A 1197 Tip comander 3-wire
  • A 1198
    A 1198 Magnetic contact probe
  • A 1199
    A 1199 Ro-adapter
  • A 1201
    A 1201 Insulated rod for CONTINUITY measurement
  • A 1202
    A 1202 Additional extension part for A 1201
  • A 1245
    A 1245 Holder for commander
  • A 1293
    A 1293 PC SW Eurotest2Mobile/Smartphone with modem and data cable
  • A 1431
    A 1431 EuroLink Android
  • A 1436
    A 1436 Bluetooth dongle
  • A 1548
    A 1548 Adapter for battery charging
  • CS 2099
    CS 2099 Eurocheck
  • S 2025
    S 2025 Test leads, 1,5 m, 2 pcs, (black, red)
  • S 2026
    S 2026 Earth test set 3 wire, 20 m
  • S 2027
    S 2027 Earth test set 3 wire, 50 m
  • S 2058
    S 2058 Insulation test plates
  • S 2080
    S 2080 A set of 6 pieces of rechargeable batteries type AA

Optional accessories:

  • A 1012
    A 1012 Test lead, green, 4 m
  • A 1018
    A 1018 Current clamp (low range leakage)
  • A 1019
    A 1019 Current clamp
  • A 1074
    A 1074 Mini current clamp 200 A - 0.2 A
  • A 1110
    A 1110 Three phase adapter
  • A 1111
    A 1111 Three phase adapter with switch
  • A 1143
    A 1143 Euro Z 290 A
  • A 1160
    A 1160 Fast charger for 6 AA batteries with a set of 6 NiMH bateries, type AA
  • A 1169
    A 1169 Fast charger for AA, C, D and 9 V block bateries
  • A 1172
    A 1172 Luxmeter sensor type B (PS/2)
  • A 1173
    A 1173 Luxmeter sensor Type C (PS/2)
  • A 1191
    A 1191 Receiver R10K
  • A 1192
    A 1192 Selective probe for R10K
  • A 1197
    A 1197 Tip comander 3-wire
  • A 1198
    A 1198 Magnetic contact probe
  • A 1199
    A 1199 Ro-adapter
  • A 1201
    A 1201 Insulated rod for CONTINUITY measurement
  • A 1202
    A 1202 Additional extension part for A 1201
  • A 1245
    A 1245 Holder for commander
  • A 1293
    A 1293 PC SW Eurotest2Mobile/Smartphone with modem and data cable
  • A 1431
    A 1431 EuroLink Android
  • A 1436
    A 1436 Bluetooth dongle
  • A 1548
    A 1548 Adapter for battery charging
  • CS 2099
    CS 2099 Eurocheck
  • S 2025
    S 2025 Test leads, 1,5 m, 2 pcs, (black, red)
  • S 2026
    S 2026 Earth test set 3 wire, 20 m
  • S 2027
    S 2027 Earth test set 3 wire, 50 m
  • S 2058
    S 2058 Insulation test plates
  • S 2080
    S 2080 A set of 6 pieces of rechargeable batteries type AA